Transient Stability Improvement on Jos – Gombe 330kV Line Using Static Var Compensator

Main Article Content

Joseph F. Udo
Maruf A. Aminu

Abstract

In this paper, the result of a study carried out to determine the impact of static VAr compensator on voltage profiles and reactive power flow in the Nigerian 330kV transmission grid network is presented. The research seeks to mitigate the challenge of high reactive power on Jos – Gombe 330kV single circuit transmission line. The high reactive power is produced in that axis as a result of low industrial demand in the North-Eastern region of Nigeria which results in low-inductive loading of the long transmission line that spans from Jos to Gombe and its extension to Yola, Damaturu and Maiduguri. The study also performed optimal placement of the static VAr compensator in the area where it can influence the voltage at the static VAr compensator device connection point by controlling the reactive power flow through the grid. This was accomplished by modeling the existing 330kV Nigerian network in DIgSILENT PowerFactory. The result is an improved power stability on the line between Jos and Gombe. The voltage tolerance with the approved Nigerian Grid Code and compliance was ensured. Also, the static VAr compensator was proposed over reactors due to the fact that it is dynamically switched.

Keywords:
Ferranti effect, DIgSILENT power factory, grid code, transient stability, voltage tolerance, optimal placement.

Article Details

How to Cite
Udo, J., & Aminu, M. (2019). Transient Stability Improvement on Jos – Gombe 330kV Line Using Static Var Compensator. Journal of Scientific Research and Reports, 24(5), 1-7. https://doi.org/10.9734/jsrr/2019/v24i530166
Section
Original Research Article

References

Purumala RR, Sinha KA, Kishore KN. Incorporation of FACTS devices in a transient stability analysis programme in National Power Systems Conference, Kharagpur; 2002.

Ogunjuyigbe ASO, Ayodele RT, Oladele OO. Improving the transient stability of Nigerian 330kV transmission network using static var comoensator part 1: The Base Study. Nigerian Journal of Technology. 2016;35(1):155-166.

Virk PS, Garg VK. Power system stability improvement of long transmission line system by using Static Var Compensator (SVC). International Journal of Engineering Research and Applications. 2013;3(5):01-03.

GmBH F. Development of power system master plan for the transmission company of Nigeria. Fichtner GmBH, Stuttgart.

Osogbo NCC. Daily Operational report, Osogbo: NCC Osogbo; 2018.

Karlsson B. Compasrison of PSS/E and Powerfactory. Degree Project in Engineering Physics, Uppsala University, Sweden; 2013.

Operator M. Transmission adequacy report: Outlook for 2017 – 2027. Transmission Company of Nigeria, Abuja; 2017.

Virk PS, Garg VK. Stability enhancement of long transmission line system by using Static Var Compensator. International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. 2013;2(9):4361-4365.

Kumkratug P. The Mathematical Model of Power System with Static Var Compensator in Long Transmission Line. American Journal of Applied Sciences. 2012;9(6):846-850.

Sutter RJ. Application of FACTS devices for power system transient stability enhancement. Master's Thesis, Jomo Kenyatta University of Agriculture and Technology, Juja, Kenya; 2016.

Saravana RKBE. Power system performance enhancement using flexible AC transmission systems devices. Master's Thesis, Memorial University of Newfoundland, Canada; 2015.

Saravana RKBE. Power system performance enhancement using flexible AC transmission systems devices. Master's Thesis, Memorial University of Newfoundland, Canada; 2015.

Yasin NM, Al-eedany M. Enhancement of power system transient stability using Static Var Compensator. International Journal.

Garg A, Agarwal SK. Dynamic stability enhancement of power transmission system using artificial neural network controlled Static Var Compensator. International Journal of Computer Applications. 2012;53(9):21-29.

Chaudhary A, Jaswal AR. Transient stability improvement of multi-machine power system using Static Var Compensator. International Journal of Electronic and Electrical Engineering. 2014;7(2):109-114.

Khasdeo A. Transient stability improvement in transmisson system using SVC with fuzzy logic. International Research Journal of Engineering and Technology. 2017;4(4): 173-177.